80KVA

Product Code HANOVER-LX3380KL
Status Call for price

Features

3:3 Phase
Low Frequency Online UPS

Specification:

MAIN FEATURES
Capacity 80kVA / 72kW
Model HANOVER-LX3380
Brand G-Mac
Brand Origin Germany
Technology Online Transformer Based Industrial UPS
INPUT
Phase 3:3
Voltage range 380/400/415Vac (-25% / +20%), (3Ph+N+PE)
Frequency range 50/60Hz (±5%)
Range Power Factor >0.97 (with filter)
OUTPUT
Output Voltage 380/400/415Vac (±1%)
Output frequency 50/60Hz (±0.05%)
THDv <3% with linear load
Crest factor 3:1 (max)
Efficiency ≥91.5%
BYPASS
Rated voltage 380/400/415Vac
Rated frequency 50/60Hz(auto-sensing)
Voltage protection range Upper limit: +20% (+10%, +15%, +20% adjustable)
Lower limit: -40% (-10%, -20%, -30%, -40% adjustable)
Frequency protection range ±10% (±2.5%, ±5%, ±10%, ±20% adjustable)
BATTERY
Battery Voltage 384Vdc
Number of Battery 12V×32Pcs
SYSTEM FEATURES
Transfer time 0ms (Line mode →Battery mode)
Overload ≤110%/60min, ≤125%/10min, ≤150%/1min, to Bypass
LED display Input, Inverter, Bypass, Battery, Output, Status
LCD display I/O voltage, frequency, power, power factor, battery voltage, current, battery status, load percentage, UPS status, history record
Communication interface Dry contact, RS232, RS485, SNMP card (Optional)
Optional Harmonic filter, SNMP adapter, LBS cables, battery temperature sensor, Bypass current-sharing inductor
ENVIRONMENT
Operating Temperature 0~40°C
Storage Temperature -25℃~55℃
Humidity Range 0~95% (Non-condensing)
Altitude <1500m
Noise level <65dB
STANDARDS
Safety IEC/EN 62040-1; IEC/EN 60950-1
Performance IEC 62040-3
EMC IEC/EN 62040-2; IEC 61000-2-2; IEC 61000-4-2; IEC 61000-4-3; IEC 61000-4-4; IEC 61000-4-5; IEC 61000-4-6; IEC 61000-4-8; IEC 61000-4-11

 

Description :

Embedded with isolated transformer, UID three-phase UPS solution raging from 10kva-120kva are designed for harsh environment especially industrial application. With a high-power factor up to 0.97,full DSP control and online double-conversion design, it can offer high levels of reliability and protection for industrial facilities and mission-critical systems, ensuring maximum power reliability.

General Features
● Online double conversion
● Full DSP control
● High power factor:0.9
● Wide input adaptability:(380Va/400Vac/415Vac) (-25%/+20%)
● Optimized battery management, self-test & flexible battery configuration 
● N+X parallel redundancy
● Strong overload capability:110%/125%/150% overload for 60/10/1min.
● Power walk-in
● Generator mode
● LBS synchronization
● Multi-protection
● User-friendly network management
 